The 2-wire transmitter uses resistance thermometers or thermocouples to acquire thetemperature. With resistance thermometers, the probe can be connected in 2-/3- or 4-wire circuit. The versions 707015/... and 707016/... are intended for installation inside the hazardous area. Probe type, connection circuit and range can be configured using the setup program. The 4 — 20mA output signal (or reversed 20 — 4mA) is available in linearized form (linear with temperature).The instrument is designed for industrial application and conforms to the corresponding European Standards, to ensure electromagnetic compatibility (EMC). The versions 707015/... and 707016/... conform to the Directives of EN 50 014, and to EN 50 020 “Electrical apparatus for use in hazardous areas” according to the Certificateof Conformity.The transmitters JUMO dTRANS T01 (Types 707011/..., 707013/... and 707016/...) can also be programmed using a HART® communicator or a HART® modem in conjunction with a PC setup program.